A step-by-step method to size an electrical panel enclosure — device list, mounting plate layout, cable space, depth and heat check — with a worked example.
Choose an enclosure too small and the panel overheats, wiring is cramped and there is no room for the next upgrade. Choose one too large and you pay for steel, floor space and cooling you never use. This guide gives a step-by-step method to size an electrical panel enclosure — width, height and depth — with a worked example.
Start from the single-line diagram and bill of materials. For every device note its width, height, depth, mounting (DIN rail, plate or door) and heat loss in watts from the datasheet:
Group devices into rows, usually power at the top or one side and control and PLC away from VFD cables. Between rows, allow for wiring ducts (trunking) — commonly 40–80 mm wide depending on the number of wires — and keep the clearances the device makers specify above and below breakers, drives and power supplies for heat and arc gases.
A simple way to add it up:
Depth is set by the deepest device (often a VFD, MCCB with a rotary handle, or a PLC with connectors), plus the distance from the mounting plate to the back of the enclosure, plus clearance in front for wiring, door-mounted devices behind the door and any rotary handle shafts. Check door-mounted devices do not hit internal equipment when the door closes.
A layout that fits may still overheat. Add up the heat losses and check whether the enclosure surface can get rid of them:
Heat the walls can dissipate ≈ k × A × ΔT
with k ≈ 5.5 W/m²·K for painted sheet steel, A the effective surface area in m² and ΔT the allowed temperature rise inside above ambient. If losses are higher, you need a larger enclosure, vents, fans or cooling — see why electrical panels overheat.
A small motor control panel holds: a 63 A MCCB incomer, 6 MCBs, 4 contactor-overload starters, a 24 V power supply, a compact PLC with 2 I/O modules, 10 relays and 40 terminals. The door carries a voltmeter, ammeter and 8 push buttons and lamps.
| Row | Contents | Width used | Height incl. duct |
|---|---|---|---|
| 1 | MCCB + 6 MCBs | about 300 mm | about 160 mm |
| 2 | 4 contactor-overload starters | about 260 mm | about 200 mm |
| 3 | Power supply + PLC + I/O + relays | about 430 mm | about 160 mm |
| 4 | 40 terminals | about 280 mm | about 120 mm |
| Total plus 25 % spare and cable space | plate width ≈ 500 mm | plate height ≈ 800 mm | |
A mounting plate of about 500 × 800 mm fits in a standard 600 W × 1000 H × 300 D mm wall-mounting enclosure, with space below for the gland plate and cable bending. The depth of 300 mm covers the PLC and MCCB plus wiring. The devices lose roughly 70 W in total. A wall-mounted 600 × 1000 × 300 mm steel enclosure has about 1.6 m² of effective cooling surface, so with a 10 K rise allowed its walls can get rid of about 5.5 × 1.6 × 10 ≈ 90 W — the heat check passes. Add a 5.5 kW VFD (often well over 100 W of losses) and filter fans or a larger enclosure would be needed.
The figures are illustrative — always use the actual device dimensions and heat losses from the datasheets.
Once you have the minimum internal size, pick the next standard enclosure size up. Standard wall-mounting and floor-standing sizes are quicker to supply and have matching mounting plates, gland plates and accessories. Custom sizes make sense when space on site is tight or the panel is repeated in large numbers.