About this calculator
A free voltage drop calculator for electrical engineers, panel builders and contractors
Why We Included a Voltage Drop Calculator on the VERCHO Website
At VERCHO Engineering Solutions, our objective is not limited to supplying electrical and mechanical products. We also aim to provide practical engineering resources that are useful to electrical engineers, consultants, panel builders, contractors and maintenance teams.
Every feeder that leaves a panel has to answer one question before the cable is ordered: will the equipment at the far end still get enough voltage? Cables have resistance and, on AC circuits, reactance. As current flows along the run, part of the supply voltage is lost in the cable itself — so a motor 120 m from the MCC never sees the full 415 V the transformer delivers.
Our Voltage Drop Calculation Tool works out that loss for DC, single-phase and three-phase circuits, checks it against the limit, and shows the smallest standard cable that works — and what each size costs you in wasted energy every year.
Why Voltage Drop Matters
A little voltage drop is unavoidable. Too much causes problems that are often blamed on the equipment instead of the cable:
- Motors — an induction motor’s torque falls roughly with the square of the voltage. Low voltage means more current, more heat and a shorter winding life, and at start-up it can mean a motor that stalls or will not accelerate its load.
- Contactors and relays can chatter or drop out when the voltage dips during a large motor start.
- Lighting dims and flickers; drives, PLCs and electronics trip on undervoltage.
- Energy — every volt lost in the cable is power turned into heat, paid for on every bill for the life of the installation.
How Is This Relevant to VERCHO?
Every one of these feeders starts and ends in an enclosure. VERCHO designs and manufactures the electrical enclosures, control panels, junction boxes, gland plates, panel locks, hinges and fasteners that the cables run into. The cable size decides the gland size, the gland plate cut-outs, the terminal space and the bending room inside the panel — so getting the cable right early saves rework on the enclosure later. For panel builders, the circuit schedule from this tool is a quick check of every outgoing feeder before the panel layout is frozen.
A Worked Example
A 37 kW motor (efficiency 92 %, power factor 0.85) is started direct-on-line from an MCC at 415 V, 50 Hz. The route is 120 m of 70 mm² copper XLPE cable. The calculator gives:
| Result | Value |
| Full-load current | 65.8 A |
| Voltage drop in the cable | 4.55 V · 1.10 % |
| Voltage at the motor | 410.4 V |
| Starting current (6 × FLC) and starting drop | 395 A · 3.54 % |
| Cable power loss | 533 W |
| Cost of losses (6,000 h/yr at ₹ 8/kWh) | ₹ 25,586 per year |
| Maximum length for a 5 % limit | 547 m |
Now suppose the MCC is itself fed through a main and sub-main feeder that already use 2 % of the limit. A 16 mm² cable, which passes on its own at 4.26 %, now fails at 6.26 %. 25 mm² just passes at 4.75 %, with almost no margin left. That is why the calculator asks for the upstream drop.
The Smallest Cable Is Not Always the Cheapest
For the same motor, here is what each copper size costs in losses at 6,000 operating hours a year:
| Size | Total drop | Starting drop | Loss | Loss cost / year |
| 16 mm² | 4.26 % | 10.31 % | 2,287 W | ₹ 1,09,789 |
| 25 mm² | 2.75 % | 7.10 % | 1,446 W | ₹ 69,406 |
| 35 mm² | 2.02 % | 5.57 % | 1,042 W | ₹ 50,026 |
| 50 mm² | 1.53 % | 4.53 % | 770 W | ₹ 36,946 |
| 70 mm² | 1.10 % | 3.54 % | 533 W | ₹ 25,586 |
| 95 mm² | 0.83 % | 2.97 % | 384 W | ₹ 18,425 |
16 mm² meets the drop limit, but wastes over ₹ 80,000 a year more than 70 mm² on this feeder. On long, heavily loaded circuits, one or two sizes up often pays for itself in a short time. Losses here are worked out at the same conductor temperature for every size; a larger cable actually runs cooler, so the real saving is slightly higher. The size table in the calculator shows this comparison for every standard size — click a size to use it.
What the Voltage Drop Calculator Works Out
- Load current from A, kW, kVA or motor HP — for motors, kW and HP are treated as rated shaft output and divided by the efficiency.
- Voltage drop in the cable, the total drop from the supply origin including upstream feeders, and the voltage at the load.
- Motor starting drop for direct-on-line, star-delta, soft starter and VFD starting, with typical starting current and power factor that you can overwrite.
- Cable rating check — the derated current rating against the load current, and the breaker or fuse rating between the two.
- Cable power loss, energy lost per year and its cost at your tariff.
- Minimum standard cable size and maximum run length for the limit.
- A circuit schedule for a whole panel or project — save it as a project file, and download it as PDF or Excel.
Why Have We Included This Tool?
VERCHO is not only a supplier of industrial products; we aim to support engineers and project teams with practical engineering resources. This calculator joins our pump head, pipe size, tank volume and bolt torque tools, and our guides to switchgear panel construction and IP ratings.
The calculator is intended as a preliminary engineering reference and should not be considered a substitute for detailed design, cable manufacturer data, IS 732 / IEC 60364 requirements or project-specific engineering calculations.
Have a question about cable sizing or an enclosure for your feeders? Use the Ask a question button or write to info@verchogroup.com.